Programming an AC inverter is the most critical task after wiring a motor. Many beginners assume that once the inverter powers up, it will automatically run the motor correctly. In real industrial environments, this assumption leads to frequent faults, unstable operation, and premature motor damage.
Incorrect inverter programming is one of the main causes of:
-
Overcurrent and overvoltage trips
-
Motor overheating
-
Mechanical shock to gearboxes and belts
-
Poor speed accuracy
-
Unnecessary energy losses
This article focuses only on AC inverter programming, from factory reset to advanced tuning. It explains not only which parameters to set, but also why they exist, how they interact, and how to verify correctness using equations and real commissioning logic.
The goal is to help beginners think like professional commissioning engineers.

Programming Strategy Used by Professionals
Experienced engineers never program inverters randomly. They follow a strict sequence:
-
Factory reset and clean setup
-
Motor rated data configuration
-
Frequency and voltage limits
-
Acceleration and deceleration behavior
-
Command and speed reference sources
-
Protection settings
-
No-load and load testing
-
Advanced tuning and optimization
-
Documentation and backup
Following this sequence avoids 90% of inverter problems.
Step 1: Factory Reset and Initial Preparation
Why Factory Reset Is Mandatory
Inverters may contain:
-
Old motor data
-
Hidden test parameters
-
Modified protection limits
A factory reset ensures a known, stable starting point.
Typical Reset Process
After reset:
-
Control source returns to default
-
Frequency reference resets
-
Protection values normalize
Always confirm reset completion before continuing.
Step 2: Motor Rated Data Programming (Foundation Step)
The inverter internally builds a motor model.
This model depends entirely on accurate nameplate data.

Mandatory Motor Parameters
| Parameter | Why It Is Critical |
|---|---|
| Rated Voltage | Correct V/F scaling |
| Rated Current | Overload and current limit |
| Rated Frequency | Base speed reference |
| Rated Speed | Slip calculation |
| Rated Power | Thermal model |
Example Motor Data Entry
Speed Verification Equation
For a 4-pole motor at 50 Hz:
Slip:
This confirms the motor data is realistic.
Step 3: Base Frequency and Maximum Frequency
Base Frequency
-
Set equal to motor rated frequency
This is where rated voltage and rated torque are achieved.
Maximum Frequency
-
Beginners should keep it equal to base frequency
Increasing maximum frequency:
-
Increases speed
-
Reduces available torque
-
Increases mechanical stress
Step 4: Minimum Frequency Setting
Minimum frequency prevents unstable operation at very low speed.
Why It Matters
At low frequency:
-
Cooling decreases
-
Torque becomes unstable
-
Motor may vibrate or stall
Recommended Values
If vibration occurs → increase minimum frequency.
Step 5: Voltage–Frequency (V/F) Curve Configuration
To maintain constant torque:
Linear V/F Curve (Most Applications)
Example motor:
-
400 V at 50 Hz
At 25 Hz:
Incorrect V/F causes:
-
High current (too much voltage)
-
Torque loss (too little voltage)
Step 6: Acceleration Time Programming
Acceleration time defines how quickly frequency increases from zero.
Why Acceleration Is Critical
Fast acceleration causes:
-
High inrush current
-
Mechanical shock
-
Overcurrent trips
Typical Acceleration Times
| Application | Time |
|---|---|
| Fans | 5–10 s |
| Pumps | 10–15 s |
| Conveyors | 15–25 s |
| High inertia | 20–40 s |
Example:
Step 7: Deceleration Time and Regenerative Energy
During deceleration, the motor acts as a generator.
What Happens Physically
-
Mechanical energy converts to electrical energy
-
DC bus voltage rises
-
Overvoltage trip occurs
Safe Deceleration
If fast stopping is required:
-
Enable DC braking
-
Install braking resistor
Step 8: Start/Stop Command Source
The inverter must know where commands come from.

Beginner Recommendation
This simplifies testing and troubleshooting.
External push buttons or PLC control should be added later.
Step 9: Speed Reference Configuration
Speed reference defines the desired motor speed.
Common Sources
| Source | Signal |
|---|---|
| Keypad | Digital |
| Potentiometer | 0–10 V |
| PLC | 4–20 mA |
Potentiometer Scaling Example
Incorrect scaling leads to limited or unstable speed control.
Step 10: Direction Check and Rotation Verification
After first run:
-
Verify motor direction
-
Ensure it matches mechanical requirements
If incorrect:
-
Change direction parameter or
-
Swap any two motor output phases
Never swap input supply phases.
Step 11: No-Load and Load Testing
No-Load Test
-
Run at 10–20 Hz
-
Current should be 30–40% of rated
Load Test
-
Increase frequency gradually
-
Monitor:
-
Output current
-
Motor temperature
-
Vibration and noise
-
If current exceeds rated:
-
Increase acceleration time
-
Reduce load
-
Recheck motor data
Advanced AC Inverter Programming Parameters
⚠️ Adjust advanced parameters only after basic operation is stable
1. Motor Auto-Tuning
Auto-tuning allows the inverter to measure real motor characteristics.
Benefits
-
Improved torque accuracy
-
Better low-speed stability
-
More precise current control
Types
| Type | Rotation | Use |
|---|---|---|
| Static | No | Safe initial tuning |
| Dynamic | Yes | High precision |
Best practice:
-
Disconnect load
-
Perform static tuning first
-
Save parameters afterward
2. Slip Compensation
As load increases, motor speed drops due to slip.
Slip compensation automatically corrects this.
Slip Equation
Typical Setting
Used in:
-
Conveyors
-
Mixers
-
Extruders
3. Torque Boost (Low-Frequency Boost)
At low speed, voltage drops and torque weakens.
Torque boost increases voltage slightly at low frequency.
Typical Setting
Too much boost causes overheating and overcurrent.
4. Current Limit and Stall Prevention
Instead of tripping, the inverter limits current and reduces speed.
Typical Range
Used in:
-
Crushers
-
Feed conveyors
-
Heavy-load systems
5. Electronic Thermal Overload (I²t Protection)
Motor heating is calculated as:
Overload Class Selection
| Class | Application |
|---|---|
| 10 | Low inertia |
| 20 | Medium inertia |
| 30 | High inertia |
Wrong selection causes false trips or motor damage.
6. Carrier Frequency (PWM Frequency)
Effect of Carrier Frequency
| Increase | Result |
|---|---|
| Noise | Decreases |
| Inverter heat | Increases |
| Efficiency | Decreases |
Typical Value
7. DC Braking Parameters
DC braking injects DC into the motor to stop it quickly.
Parameters
-
DC braking start frequency
-
DC voltage level
-
Braking time
Used in:
-
Positioning conveyors
-
Cutting machines
-
Packaging equipment
8. Flying Start (Catch-on-the-Fly)
Allows the inverter to synchronize with a rotating motor.
Applications
-
Power loss recovery
-
Fans and pumps
-
High-inertia loads
Prevents overcurrent during restart.
9. Preset Speeds (Multi-Speed Control)
Allows fixed speeds without analog signals.
Example:
Used in washing systems and indexing conveyors.
Practical Programming Projects
Project 1: Variable-Speed Conveyor
-
Min freq: 5 Hz
-
Max freq: 45 Hz
-
Accel: 18 s
-
Decel: 22 s
Project 2: Energy-Saving Pump
Pump power relationship:
Reducing speed to 80%:
➡ Nearly 49% energy saving
Common Programming Mistakes
| Mistake | Result |
|---|---|
| Wrong motor current | Frequent trips |
| Fast acceleration | Overcurrent |
| No slip compensation | Speed drop |
| Excess torque boost | Overheating |
Commissioning Checklist
✔ Factory reset completed
✔ Motor data verified
✔ Accel/decel tested
✔ Rotation confirmed
✔ Current within limits
✔ Parameters backed up
Conclusion
Programming an AC inverter is a structured engineering process, not trial and error. When parameters are entered logically—starting from motor data, followed by frequency control, dynamic behavior, and advanced tuning—the inverter becomes a reliable, efficient, and safe control system.
Mastering inverter programming gives beginners:
-
Professional commissioning skills
-
Reduced downtime
-
Energy efficiency expertise
-
Strong automation foundation
AC Inverter Communication
Why Communication Is Important in AC Inverter Programming
In modern automation systems, an AC inverter rarely works alone. Instead of using only local keypads or simple push buttons, inverters are commonly connected to PLCs, HMIs, SCADA systems, and industrial networks. Communication allows centralized control, monitoring, diagnostics, and integration into automated production lines.

Without correct communication settings, even a perfectly programmed inverter will:
-
Ignore speed commands
-
Fail to start or stop remotely
-
Show incorrect status on HMI
-
Generate communication faults
Therefore, communication programming is a core part of inverter commissioning, not an optional feature.
Basic Communication Concept in Inverters
Communication replaces traditional control wiring.
Without Communication
-
Digital inputs → Start / Stop
-
Analog input → Speed reference
-
Limited feedback
With Communication
-
Start/Stop via network
-
Speed reference via network
-
Real-time feedback (frequency, current, alarms)
-
Fault diagnostics
-
Parameter access
This reduces wiring, improves reliability, and increases flexibility.
Common Industrial Communication Protocols Used with Inverters
Most AC inverters support one or more of the following protocols:
| Protocol | Typical Use |
|---|---|
| Modbus RTU | Simple PLC & HMI systems |
| Modbus TCP | Ethernet-based systems |
| Profibus | Siemens automation |
| Profinet | High-speed Ethernet |
| EtherNet/IP | Allen-Bradley systems |
| CANopen | Motion and compact systems |
| RS-485 (physical layer) | Used by Modbus RTU |
For beginners, Modbus RTU is the most common and easiest to start with.
Communication Hardware Setup (Physical Layer)
Typical RS-485 Wiring (Modbus RTU)
-
Two data lines: A (+) and B (–)
-
Optional signal ground
-
Daisy-chain topology (not star)
Wiring Rules
-
Use twisted pair cable
-
Avoid long stubs
-
Use termination resistor at the last device
-
Keep cable away from power lines
Incorrect wiring causes:
-
Intermittent communication
-
Random faults
-
No response from inverter
Step 1: Selecting Communication as Control Source
Before communication works, the inverter must be told to accept commands from the network.
Typical Parameters
If this step is missed:
-
PLC sends commands
-
Inverter ignores them
-
Motor does not run
This is one of the most common beginner mistakes.
Step 2: Communication Address (Node ID / Slave ID)
Each inverter on a network must have a unique address.
Example
Rules:
-
No two devices share the same address
-
Address range depends on protocol (often 1–247 for Modbus)
Duplicate addresses cause communication failure for all devices.
Step 3: Communication Speed (Baud Rate)
Baud rate defines how fast data is transmitted.
Common Baud Rates
-
9600
-
19200
-
38400
-
57600
Example
Important:
-
PLC, HMI, and inverter must match exactly
-
Higher speed is not always better for noisy environments
Step 4: Data Format (Parity, Data Bits, Stop Bits)
All devices must use the same data format.
Typical Modbus RTU Setting
Mismatch causes:
-
Communication timeouts
-
CRC errors
-
Unstable connection
Step 5: Communication Timeout and Fault Response
Communication timeout defines how long the inverter waits for valid data.
Example
If communication is lost:
-
Inverter can stop the motor
-
Hold last speed
-
Trigger fault
Recommended Behavior for Safety
This prevents uncontrolled operation.
Control Word and Status Word Concept
Most communication protocols use control words and status words.
Control Word (Sent to Inverter)
Controls:
-
Start / Stop
-
Direction
-
Reset faults
Status Word (Sent from Inverter)
Provides:
-
Run status
-
Fault status
-
Ready state
-
Direction feedback
Example Logic
-
PLC sends Start bit = 1
-
Inverter runs motor
-
Inverter returns Running bit = 1
This handshake confirms correct operation.
Speed Reference via Communication
Instead of analog signals, speed is sent digitally.
Example (Modbus)
-
Speed register value = 2500
-
Scaling:
So:

Incorrect scaling causes:
-
Wrong motor speed
-
Sudden jumps
-
Operator confusion
Always confirm scaling parameters.
Monitoring Data via Communication
Communication allows real-time monitoring of:
| Parameter | Benefit |
|---|---|
| Output frequency | Speed verification |
| Motor current | Load monitoring |
| DC bus voltage | Power quality |
| Fault codes | Fast diagnostics |
| Run hours | Maintenance planning |
This data is critical for predictive maintenance.
Fault Handling and Diagnostics Over Communication
When a fault occurs:
-
Inverter sends fault code
-
PLC or HMI displays alarm
-
Maintenance reacts faster
Example Fault Actions
-
Overcurrent → increase acceleration time
-
Overvoltage → increase deceleration time
-
Overload → check mechanical load
Communication drastically reduces troubleshooting time.
Multi-Inverter Communication Systems
In large systems:
-
One PLC controls multiple inverters
-
Each inverter has a unique address
-
Same network, same protocol
Example
This reduces:
-
Wiring
-
Panel size
-
Commissioning time
Common Communication Problems and Solutions
| Problem | Cause | Solution |
|---|---|---|
| No response | Wrong address | Check node ID |
| Intermittent fault | Noise | Improve grounding |
| CRC errors | Wrong parity | Match settings |
| Drive won’t run | Wrong control source | Select communication |
| Wrong speed | Scaling mismatch | Correct parameters |
Best Practices for Reliable Inverter Communication
✔ Use shielded twisted pair cable
✔ Ground shields at one point only
✔ Match all communication parameters
✔ Document register addresses
✔ Test with one inverter first
✔ Save parameter backup
Why Communication Programming Matters (Industrial Insight)
From real industrial installations:
-
Over 40% of commissioning delays are communication-related
-
Most issues are parameter mismatches, not hardware faults
-
Proper communication setup reduces downtime dramatically
Correct communication turns an inverter into a smart field device, not just a motor driver.
Final Note
Communication programming is the bridge between standalone motor control and full automation systems. When configured correctly, it enables centralized control, accurate monitoring, fast diagnostics, and future system expansion.